Optimum Shape Design of Metal-Enclosed 550 kV Disconnectors Based on Response Surface Method and Finite Element Analysis

Authors

  • R. Gong School of Electrical Engineering, Xi’an Jiaotong University, China
  • S. Wang School of Electrical Engineering, Xi’an Jiaotong University, China
  • X. Luo School of Electrical Engineering, Xi’an Jiaotong University, China
  • M. Danikas Department of Electrical & Computer Engineering, Democritus University of Thrace, Greece
Volume: 5 | Issue: 4 | Pages: 818-824 | August 2015 | https://doi.org/10.48084/etasr.567

Abstract

In this paper, the optimum shape design of 550 kV disconnectors in Gas Insulated Switchgears (GIS) are firstly presented employing the Finite Element Method (FEM) for electric field analysis coupled with an optimal design method. For effective analysis, the FEM is conducted in transient quasistatic electric field, using a finite element FORTRAN code. The structure parameters of disconnectors that provide the required electric field strength are obtained by the Response Surface Method (RSM) and the optimal values are presented by the variation in maximal electric field strength. The RSM and optimal design methods are also conducted by FORTRAN codes. The optimal result reveals that a uniform electric field distribution is achieved in 550 kV disconnectors. Additionally, the optimal result of disconnectors is verified by the proposed disconnector undertaken power frequency withstanding voltage of 740 kV for 1 minute, lightening impulse of 1675 kV, and operating impulse of 1300 kV, respectively.

Keywords:

Disconnectors, response surface method, RSM, optimization, structure design, finite element method, FEM

Downloads

Download data is not yet available.

References

G. Zhang, Finite Element Method, Beijing, Mechanical Industry Press, 1991

J. Sheng, Numerical analysis of electromagnetic field. Xi’an, Xi’an Jiaotong University Press, 1991

Y. J. Kim, J. D. Lee, B. J. Lee, H. K. Shin, S. C. Hahn, “Design optimization of permanent magnetic actuator for vacuum circuit breaker by response surface method”, International Conference on Electrical Machines and Systems (ICEMS), pp. 1-4, Saporo, Japan, October 21-24, 2012

K. W. Jeon, T. K. Chung, S. C. Hahn, “NEMA class a slot shape optimization of induction motor for electric vehicle using response surface method”, International Conference on Electrical Machines and Systems (ICEMS), pp. 1-4, Beijing, China, August 20-23, 2011 DOI: https://doi.org/10.1109/ICEMS.2011.6073692

B. H. Lee, K. S. Kim, J. P. Hong, J. H. Lee, “Optimum shape design of single-sided linear induction motors using response surface methodology and finite-element method”, International Conference on Electrical Machines and Systems (ICEMS), pp. 1-5, Beijing, China, August 20-23, 2011 DOI: https://doi.org/10.1109/ICEMS.2011.6073769

L. Egiziano, V. Tucci, C. Petrarca, M. Vitelli, “A Galerkin model to study the field distribution in electrical components employing nonlinear stress grading materials”, IEEE Transactions on Dielectrics and Electrical Insulation, Vol. 6, No. 6, pp. 765-773, 1999 DOI: https://doi.org/10.1109/94.822012

J. Kuang, J. D. Lavers, S. Boggs, “Program for transient nonlinear finite element analysis with applications to coupled field programs”, 10th International Symposium on High Voltage Engineering, Montreal Quebec, Canada, pp. 25-29, 1997

X. Ma, Electromagnetic theory and applications, Xi’an, Xi’an Jiaotong University Press, 2000

G. Lupo, G. Miano, V. Tucci, M. Vitelli. “Field distribution in cable terminations from a quasi-static approximation of the Maxwell equations”, IEEE Transactions on Dielectrics and Electrical Insulation, Vol. 3, No. 3, pp. 399-409, 1996 DOI: https://doi.org/10.1109/94.506213

Z. Zhang, B. Xiaofeng, “Comparison about the three central composite designs with simulation. advanced computer control”, International Conference on Advanced Copmuter Control (ICACC), Singapore, pp. 163-167, January 22-24, 2009 DOI: https://doi.org/10.1109/ICACC.2009.48

C. Petrarca, L. Egiziano, V. Tucci, M. Vitelli “Impulse performances of cable terminations employing stress grading accessories”, 1999 Annual Report Conference on Electrical Insulation and Dielectric Phenomena, Austin, USA, Vol. 1, pp. 146-149, October 17-20, 1999

B. Li, SF6 High Voltage Apparatus, Beijing, Mechanical Industry Press, 2008

Downloads

How to Cite

[1]
R. Gong, S. Wang, X. Luo, and M. Danikas, “Optimum Shape Design of Metal-Enclosed 550 kV Disconnectors Based on Response Surface Method and Finite Element Analysis”, Eng. Technol. Appl. Sci. Res., vol. 5, no. 4, pp. 818–824, Aug. 2015.

Metrics

Abstract Views: 781
PDF Downloads: 280

Metrics Information

Most read articles by the same author(s)

<< < 1 2 3